1. Introduction
1 - 3
1-1-2 Unit outline type
Unit outline
type
B1 C1 D1/D2
Outline
dimensions
[mm]
H:380
200
W:90
D:260
Fin
Wiring allowance at front: 50mm
Required ventilation space at back:
15mm
H:380
200
W:120
D:260
Fin
Wiring allowance at front: 50mm
Required ventilation space at back:
15mm
H:380
200
W:150
D:260
/
263
Fin
Wiring allowance at front: 50mm
Required ventilation space at back:
15mm (D2: 12mm)
Heat dissipa-
tion method
Heat radiated outside panel
(forced wind cooling)
Heat radiated outside panel
(forced wind cooling)
Heat radiated outside panel
(forced wind cooling)
(Note) Refer to "Appendix 1 Outline dimension drawings" for detailed outline drawings.
For customers switching from MDS-A/B Series
The MDS-C1-SPA Series incorporates a highly efficient heat dissipating structure, so the depth of the fin
section is smaller than the MDS-A/B Series. Units with an "S" at the end of the type have a smaller unit
width than the MDS-A/B Series.
When designing the control panel with these unit outline dimensions, it may not be possible to mount the
conventional drive unit.